NEURO-FUZZY MEASUREMENT MODELS FOR THE METROLOGICAL ASSURANCE OF COMPLEX MOISTURE TEMPERATURE–PRESSURE MONITORING IN ANAEROBIC DIGESTION

Authors

  • Abdullayev Husniddin Associate Professor, Doctor of Philosophy (PhD) in Engineering, Renaissance University, Uzbekistan Author
  • Aziza Navruzova Doctoral student, Bukhara State Technical University, Bukhara, Uzbekistan e-mail: husniddin.abdullayev9395@gmail.com Author

Keywords:

metrological assurance; measurement uncertainty; ANFIS; multivariate measurement; dielectric moisture sensing; biogas; calibration.

Abstract

Reliable monitoring of anaerobic digestion requires simultaneous measurement of moisture W, temperature T and pressure P of a heterogeneous biomass, yet the three channels interact and no certified reference materials exist for the matrix. We formulate this as a multivariate measurement problem, y = F(x, θ), in which an ANFIS/ANN model compensates cross-influences and the uncertainty is propagated through the model (JCGM 101/102). Using a preliminary laboratory data set, we show that (i) a linear dielectric calibration is physically inconsistent and yields U95(W) ≈ 11–12 % absolute, whereas a refractive (√ε′) calibration reduces it to ≈ 7–8 %; (ii) the substrate (matrix) explains 95.8 % of CH4 variance against 1.3 % for W, T, P together, so data-driven models do not transfer between matrices (leave-one-substrate-out RMSE ≈ 10.8 % points ≈ the data SD). A 100-run factorial design with independent pressure control and hold-out validation is proposed.

References

[1] JCGM 100:2008. Evaluation of measurement data – Guide to the expression of uncertainty in measurement (GUM).

[2] JCGM 101:2008. Evaluation of measurement data – Supplement 1 to the GUM – Propagation of distributions using a Monte Carlo method.

[3] JCGM 102:2011. Evaluation of measurement data – Supplement 2 to the GUM – Extension to any number of output quantities.

[4] JCGM 200:2012. International vocabulary of metrology – Basic and general concepts and associated terms (VIM), 3rd ed.

[5] ISO/IEC 17025:2017. General requirements for the competence of testing and calibration laboratories.

[6] Jang J.-S. R. ANFIS: adaptive-network-based fuzzy inference system. IEEE Trans. Syst. Man Cybern., 1993, 23(3), 665–685.

[7] Takagi T., Sugeno M. Fuzzy identification of systems and its applications to modeling and control. IEEE Trans. Syst. Man Cybern., 1985, SMC-15(1), 116–132.

[8] Birchak J. R., Gardner C. G., Hipp J. E., Victor J. M. High dielectric constant microwave probes for sensing soil moisture. Proc. IEEE, 1974, 62(1), 93–98.

[9] Topp G. C., Davis J. L., Annan A. P. Electromagnetic determination of soil water content. Water Resour. Res., 1980, 16(3), 574–582.

[10] Kalandarov P. I., Abdullaev Kh. Kh. Features of the technology of anaerobic processing of biotails using humidity control devices. IOP Conf. Ser.: Earth Environ. Sci., 2022, vol. 1043, art. 012011. https://doi.org/10.1088/1755-1315/1043/1/012011

[11] Kalandarov P., Tursunov O., Abdulloev H., Karimov I. The effect of biomass moisture on the intensity of the fermentation process in biogas production. AIP Conf. Proc., 2023, vol. 2741, art. 050014. https://doi.org/10.1063/5.0130084

[12] Kalandarov P. I., Abdullaev Kh. Kh., Khaitov A. N., Sharifov Kh. S., Murodova G. F. Modeling of biotechnological objects. BIO Web Conf., 2024, vol. 108, art. 25005. https://doi.org/10.1051/bioconf/202410825005

[13] Kalandarov P. I., Mukimov Z. M., Abdullaev H. H., Yusupov N. O. Metrological support of moisture measurements of agricultural materials. Int. J. Aquatic Science, 2021, vol. 12, no. 2, pp. 4870–4875.

Downloads

Published

2026-11-16